Pharos

Pharos
Pharos RIO D
A product change notification applies to this product, click here to read more The Pharos Designer RIO D (Remote Input Output DALI) device provides a convenient and scalable way to control DALI fixtures and ballasts from a Pharos Designer control system. Pharos Designer Remote Devices can be used with the full range of Pharos Designer Controllers, providing…
- Product code
- RIO-D
- Category
- Lighting
- Family
- remote-devices
Specifications
Capabilities
- DALI Control
- Control for up to 64 DALI devices including device discovery and configuration
- DALI Receive
- Receive DALI messages from other controllers such as wall panels or occupancy sensors
- Emergency Lighting
- Emergency Lighting Schedule automatic Function and Duration tests; automatic querying for battery level and lamp hours; test result and error reporting web page
- Bus Power Detection
- Detect and report bus power status, a separate DALI bus power supply is required
Interfaces
- Ethernet
- RJ45 socket for 10/100Base-TX Ethernet with Link/Data LEDs; Fixed IP or DHCP; Power-over-Ethernet (PoE)
- DALI
- Port can transmit and receive DALI commands *; Supports DALI standards: EN 62386-101:2009, EN 62386-102:2009, EN 62386-202:2009, EN 62386-209:2011
System Limits
- In Project
- Maximum 200 remote devices across multiple controllers in a single Pharos Designer project.
- Per Controller
- Maximum remote device limits assigned to controllers depend on controller type:; 64 for each LPC 1, 2, 4 , and TPC; 100 for each LPC X , VLC and VLC+
- DALI Interface per Controller
- Maximum total configured DALI ports assigned to controllers depend on controller type:; 16 for each LPC 1 and TPC; 32 for each LPC 2; 64 for each LPC 4; 100 for each LPC X; 100 for each VLC and VLC+ (for triggering only)
- Certifications
- CE compliant, UKCA compliant, ETL/cETL listed
- Power
- PoE (IEEE802.3af, Class 1), 1.5W typical
- Required
- Any Pharos Designer Controller
- Configuration
- Pharos Designer 2
- Addressing
- By rotary selector switch
- Temperature
- 0°C to 50°C (32°F to 122°F)
- Humidity
- 10-50% relative, non-condensing
- Ingress
- IP40
- Physical
- 4 unit wide DIN rail mounting enclosure (DIN43880 / EN60715 (35/7.5 rail)); 7.2 x 9 x 5.8 cm (2.8 x 3.5 x 2.3 in); 0.3 kg (0.7 lbs)
- Shipping
- 20 x 15 x 12 cm (8 x 6 x 5 in); 0.5 kg (1.1 lbs)
- Recovery
- Hardware watchdog and recessed reset button
- Warranty
- 5 years